Technical Guide · IS 694:2010

FR vs
FR-LSH.

FR stands for Flame Retardant; FR-LSH, also written FRLSH, stands for Flame Retardant Low Smoke and Halogen. Both are PVC wires under IS 694:2010 with identical flame retardance — Oxygen Index ≥ 29%, Temperature Index ≥ 250°C — and the same 70°C conductor temperature and 1100 V grade. The difference is two combustion limits FR does not have: FR-LSH must not exceed 20% halogen acid gas (IS 10810 Part 59) and a 60% smoke density rating (IS 13360 Part 6/Sec 9). Plain FR has no smoke or halogen limit in IS 694:2010.

The Short Answer

The two types — at a glance.

Standard
FR
IS 694:2010 · FR designation
✓Flame retardant — flammability test per IS 10810 (Part 53)
✓Oxygen Index ≥ 29% · Temperature Index ≥ 250°C
✗No smoke limit in IS 694:2010
✗No halogen limit in IS 694:2010
Low Smoke
FR-LSH
IS 694:2010 · FR-LSH category
✓All FR requirements — OI ≥ 29%, TI ≥ 250°C
✓Halogen acid gas ≤ 20% (IS 10810 Part 59)
✓Smoke density rating ≤ 60% (IS 13360 Part 6/Sec 9)
✗Low halogen, not halogen-free — PVC-based
Test Limits

What each standard actually requires.

PropertyFRFR-LSH
StandardIS 694:2010 (FR designation)IS 694:2010 (FR-LSH category)
InsulationPVCPVC (low-smoke, low-halogen compound)
FlammabilityIS 10810 (Part 53) — burning stops within 60 s of flame removalSame — IS 10810 (Part 53)
Oxygen Index≥ 29% — IS 10810 (Part 58)≥ 29% — IS 10810 (Part 58)
Temperature Index≥ 250°C — IS 10810 (Part 64)≥ 250°C — IS 10810 (Part 64)
Halogen acid gasNo limit in IS 694:2010≤ 20% by weight — IS 694:2010 cl. 10.6, tested per IS 10810 (Part 59)
SmokeNo limit in IS 694:2010Smoke density rating ≤ 60% — IS 694:2010 cl. 10.8, tested per IS 13360 (Part 6/Sec 9)
Conductor temperature70°C70°C
Voltage grade1100 V1100 V
BIS licenceCM/L 8800140116CM/L 8800140116
Where Each Is Specified

Selection guidance.

FR wire is specified for general residential and commercial wiring where the project specification sets no smoke or halogen condition. National Cables suggests FR-LSH for escape routes and for all areas of high-rise residential buildings — in a stairwell fire, lower smoke density protects evacuation. NBC 2016 Part 8/Sec 2 cl. 5.3.7.1 notes that FR-LSH cable is available and may be considered. The project specification governs the cable type.

⚠️ Substitution risk: FR (IS 694:2010) has no smoke or halogen limit, so it does not meet a specification that calls for FR-LSH. The cable supplied must match the category named in the BOQ.
Product & Sizing Reference

Specify by product — the National Cables range.

FR Single Core Wire — flame-retardant PVC, IS 694:2010, 0.5–240 mm². FR-LSH Single Core Wire — flame retardant, low smoke and halogen, IS 694:2010. All ranges use Class 5 conductors — strand construction and resistance limits: IEC 60228 / IS 8130:2013 conductor classes. Size selection for a given load: cable size calculator.

Related comparisons: FR-LSH vs LSZH · FR vs LSZH · full three-way comparison.

Frequently Asked Questions

FR vs FR-LSH — selection questions.

The differences between the two IS 694:2010 categories, and when each is the correct specification.

What is the difference between FR and FR-LSH wire?

Both are PVC wires under IS 694:2010 with the same flame retardance: flammability test per IS 10810 (Part 53), Oxygen Index ≥ 29%, Temperature Index ≥ 250°C.

FR-LSH adds two combustion limits: halogen acid gas ≤ 20% by weight (IS 10810 Part 59) and a smoke density rating ≤ 60% (IS 13360 Part 6/Sec 9). Plain FR has no smoke or halogen limit.

What is the full form of FR and FRLSH?

FR stands for Flame Retardant. FRLSH (FR-LSH) stands for Flame Retardant Low Smoke and Halogen. Both are categories of PVC wire under IS 694:2010.

Can FR wire be used where FR-LSH is specified?

No. FR has no smoke or halogen limit in IS 694:2010, so it does not meet a specification that calls for FR-LSH. The cable supplied must match the category named in the BOQ.

Do FR and FR-LSH have the same temperature and voltage rating?

Yes. Both are rated 70°C continuous conductor temperature at the 1100 V grade of IS 694:2010. The differentiation is fire performance, not thermal or electrical class.

Is FR-LSH halogen-free?

No. FR-LSH is a low-halogen PVC compound — IS 694:2010 permits halogen acid gas up to 20% by weight. Halogen-free cable is HFFR (LSZH) to IS 17048:2018, limited to 0.5%. See FR-LSH vs LSZH.

Specify the correct cable for your project.

Our technical team matches IS 694:2010 and IS 17048:2018 cable types to your project specification.

Request Technical Advice →