Technical Guide · IS 694:2010 · IS 17048:2018

FR-LSH vs
LSZH.

FR-LSH (FRLSH) stands for Flame Retardant Low Smoke and Halogen: a low-halogen PVC wire under IS 694:2010, limited to 20% halogen acid gas and a 60% smoke density rating. LSZH stands for Low Smoke Zero Halogen; its BIS designation is HFFR, Halogen-Free Flame Retardant, under IS 17048:2018: a non-PVC polyolefin wire limited to 0.5% halogen acid gas, with light transmittance ≥ 70% and Oxygen Index ≥ 31. The permitted halogen limits differ 40-fold, the standards differ, and the BIS licences are separate — the two are not interchangeable.

The Short Answer

The two types — at a glance.

Low Smoke
FR-LSH
IS 694:2010 · FR-LSH category
✓All FR requirements — OI ≥ 29%, TI ≥ 250°C
✓Halogen acid gas ≤ 20% (IS 10810 Part 59)
✓Smoke density rating ≤ 60% (IS 13360 Part 6/Sec 9)
✗Low halogen, not halogen-free — PVC-based
Halogen-Free
LSZH / HFFR
IS 17048:2018 · HFFR designation
✓Halogen acid gas ≤ 0.5% (IS 10810 Part 59)
✓Light transmittance ≥ 70% (IS 10810 Part 63)
✓Oxygen Index ≥ 31 · combustion gas pH ≥ 4.3
✓Non-PVC polyolefin — contains no chlorine or bromine
Test Limits

What each standard actually requires.

PropertyFR-LSHLSZH / HFFR
StandardIS 694:2010 (FR-LSH category)IS 17048:2018
InsulationPVC (low-smoke, low-halogen compound)Non-PVC polyolefin — no chlorine or bromine
Halogen acid gas≤ 20% by weight — IS 10810 (Part 59)≤ 0.5% — IS 10810 (Part 59)
Combustion gas acidityNot specifiedpH ≥ 4.3, conductivity ≤ 10 µS/mm (Annex D)
Smoke testSmoke density rating ≤ 60% — IS 13360 (Part 6/Sec 9)Light transmittance ≥ 70% — IS 10810 (Part 63)
Oxygen Index≥ 29%≥ 31
Temperature Index≥ 250°C≥ 250°C
Conductor temperature70°C70°C — thermoplastic (HFI-TP 70)
BIS licenceCM/L 8800140116CM/L 8800227819
Where Each Is Specified

Selection guidance.

FR-LSH is the common escape-route and high-occupancy specification — National Cables suggests it for stairwells and all areas of high-rise residential buildings. LSZH/HFFR is specified where the project limits halogen acid gas to 0.5%: underground metro stations, data centres, and hospital tenders commonly carry that condition, because hydrogen chloride corrodes medical and electronic equipment even at sub-ignition temperatures.

⚠️ Substitution risk: FR-LSH (IS 694:2010) permits halogen acid gas up to 20%, so it does not meet a specification that calls for HFFR to IS 17048:2018 (≤ 0.5%). The cable supplied must match the standard named in the BOQ.
Product & Sizing Reference

Specify by product — the National Cables range.

FR-LSH Single Core Wire — flame retardant, low smoke and halogen, IS 694:2010. LSZH / HFFR Wire — halogen-free flame retardant, IS 17048:2018. All ranges use Class 5 conductors — strand construction and resistance limits: IEC 60228 / IS 8130:2013 conductor classes. Size selection for a given load: cable size calculator.

Related comparisons: FR vs FR-LSH · FR vs LSZH · full three-way comparison.

Frequently Asked Questions

FR-LSH vs LSZH — selection questions.

Low-halogen PVC versus halogen-free polyolefin, and why the two specifications are not interchangeable.

Is FR-LSH the same as LSZH?

No. Both are flame retardant, but the halogen limits are not interchangeable: FR-LSH permits up to 20% halogen acid gas per IS 694:2010, while HFFR permits up to 0.5% per IS 17048:2018 — a 40-fold difference in the permitted limit. The insulation chemistry also differs: FR-LSH is PVC-based; HFFR contains no chlorine or bromine.

What are the full forms of FRLSH, FRLSZH, and HFFR?

FRLSH (FR-LSH): Flame Retardant Low Smoke and Halogen — IS 694:2010. FRLSZH (FR-LSZH): Flame Retardant Low Smoke Zero Halogen — a trade name for the LSZH category. HFFR: Halogen-Free Flame Retardant — the designation used by IS 17048:2018.

How do the smoke tests differ between FR-LSH and LSZH?

The two standards use different smoke tests. FR-LSH: smoke density rating ≤ 60% per IS 13360 (Part 6/Sec 9), under IS 694:2010. HFFR: light transmittance ≥ 70% per IS 10810 (Part 63), under IS 17048:2018. The methods differ, so the two figures are not directly comparable.

A hospital BOQ names IS 17048:2018 — does FR-LSH comply?

No. Where a specification names IS 17048:2018, FR-LSH to IS 694:2010 does not meet it — the halogen limits differ 40-fold and the BIS licences are separate. Specify HFFR to IS 17048:2018 where the project specification limits halogen acid gas to 0.5%.

Do FR-LSH and LSZH have the same conductor temperature rating?

Yes, in the National Cables range: both are rated 70°C continuous. IS 17048:2018 rates thermoplastic HFFR insulation (HFI-TP 70) at 70°C; the 90°C rating applies only to crosslinked HFFR compounds.

Specify the correct cable for your project.

Our technical team matches IS 694:2010 and IS 17048:2018 cable types to your project specification.

Request Technical Advice →