FR stands for Flame Retardant: PVC wire under IS 694:2010 with a flammability test, Oxygen Index ≥ 29% and Temperature Index ≥ 250°C, but no smoke or halogen limit. LSZH stands for Low Smoke Zero Halogen; its BIS designation is HFFR, Halogen-Free Flame Retardant, under IS 17048:2018 — a non-PVC polyolefin compound limited to 0.5% halogen acid gas, with light transmittance ≥ 70% through its smoke and Oxygen Index ≥ 31. They are different standards, different insulation chemistries, and separate BIS licences.

The Short Answer

The two types — at a glance.

Standard
FR
IS 694:2010 · FR designation
✓Flame retardant — flammability test per IS 10810 (Part 53)
✓Oxygen Index ≥ 29% · Temperature Index ≥ 250°C
✗No smoke limit in IS 694:2010
✗No halogen limit in IS 694:2010
Halogen-Free
LSZH / HFFR
IS 17048:2018 · HFFR designation
✓Halogen acid gas ≤ 0.5% (IS 10810 Part 59)
✓Light transmittance ≥ 70% (IS 10810 Part 63)
✓Oxygen Index ≥ 31 · combustion gas pH ≥ 4.3
✓Non-PVC polyolefin — contains no chlorine or bromine
Test Limits

What each standard actually requires.

PropertyFRLSZH / HFFR
StandardIS 694:2010IS 17048:2018
InsulationPVCNon-PVC polyolefin — no chlorine or bromine
Halogen acid gasNo limit in IS 694:2010≤ 0.5% — IS 10810 (Part 59)
Combustion gas acidityNot specifiedpH ≥ 4.3, conductivity ≤ 10 µS/mm (Annex D)
SmokeNo limit in IS 694:2010Light transmittance ≥ 70% — IS 10810 (Part 63)
Oxygen Index≥ 29%≥ 31
Temperature Index≥ 250°C≥ 250°C
Conductor temperature70°C70°C — thermoplastic (HFI-TP 70)
BIS licenceCM/L 8800140116CM/L 8800227819
Where Each Is Specified

Selection guidance.

FR wire is specified for general wiring where the project specification sets no smoke or halogen condition. LSZH/HFFR is specified where the project limits halogen acid gas to 0.5% — underground metro stations, data centres, and hospital tenders commonly carry that condition, because hydrogen chloride from burning PVC corrodes electronic equipment even at sub-ignition temperatures and impairs evacuation in enclosed spaces.

⚠️ Substitution risk: FR and LSZH are different standards with separate BIS licences. FR (IS 694:2010) has no smoke or halogen limit, so it does not meet a specification that names IS 17048:2018. The cable supplied must match the standard named in the BOQ.
Product & Sizing Reference

Specify by product — the National Cables range.

FR Single Core Wire — flame-retardant PVC, IS 694:2010, 0.5–240 mm². LSZH / HFFR Wire — halogen-free flame retardant, IS 17048:2018. All ranges use Class 5 conductors — strand construction and resistance limits: IEC 60228 / IS 8130:2013 conductor classes. Size selection for a given load: cable size calculator.

Related comparisons: FR vs FR-LSH · FR-LSH vs LSZH · full three-way comparison.

Frequently Asked Questions

FR vs LSZH — selection questions.

Two different standards and insulation chemistries, and when each is the correct specification.

What is the difference between FR and LSZH wire?

FR is PVC wire under IS 694:2010 — flame retardant, but with no smoke or halogen limit. LSZH (BIS designation HFFR) is non-PVC polyolefin wire under IS 17048:2018 — halogen acid gas ≤ 0.5%, light transmittance ≥ 70%, Oxygen Index ≥ 31.

What is the full form of LSZH?

LSZH stands for Low Smoke Zero Halogen. It is also sold as FR-LSZH or FRLSZH (Flame Retardant Low Smoke Zero Halogen). The designation used by IS 17048:2018 is HFFR — Halogen-Free Flame Retardant.

Can FR and LSZH wire be interchanged?

No. They are made to different standards under separate BIS licences — CM/L 8800140116 (IS 694:2010) and CM/L 8800227819 (IS 17048:2018). FR has no smoke or halogen limit, so it does not meet a specification that names IS 17048:2018.

Why do metro stations and data centres specify LSZH rather than FR?

Burning PVC releases hydrogen chloride gas that corrodes electronic circuit boards, contacts, and metal infrastructure even at sub-ignition temperatures. LSZH/HFFR is limited to 0.5% halogen acid gas, protecting equipment during a fire elsewhere in the building. Underground metro stations carry the additional concern of evacuation in a confined space.

Is LSZH rated for a higher conductor temperature than FR?

Not in the National Cables range. IS 17048:2018 rates thermoplastic HFFR insulation (HFI-TP 70) at 70°C — the same conductor temperature as IS 694:2010 PVC. The 90°C rating applies only to crosslinked HFFR compounds, which are a different insulation grade.

Specify the correct cable for your project.