DIN VDE 0281 · 300/500V · Sheathed Building Cable · Export Range

NYM-J / NYM-O
German-standard sheathed multicore building cable.

NYM is the dominant multicore sheathed building cable in German-influenced markets — Germany, Austria, Eastern Europe, Turkey, East Africa, and the Middle East. PVC-insulated cores in a PVC outer sheath, Class 1 solid or Class 2 stranded conductor, 300/500V. Available with earth core (NYM-J) or without (NYM-O).

300/500V
Rated voltage
70°C
Max conductor temperature
1–12 core
Core count range
1.5–35mm²
Conductor size range
IS 694:2010 — BIS certified production (CM/L-8800140116). Export builds are strictly Made-to-Order (MTO), manufactured on the same certified line to a dielectric specification (1100V) that exceeds the VDE requirement.
Designation Explained

NYM — the German code system decoded.

The NYM designation follows the German VDE coding system. Each letter encodes a construction characteristic: N = Normleitung (standard cable — VDE) · Y = PVC insulation · M = PVC sheath (multiple cores, round construction). The suffix encodes earth and flexibility: J = with green/yellow earth · O = without earth (Ohne Schutzleiter) · K = flexible Class 5 conductors (paired with J or O for earth variants).

VariantConductor classEarth corePrimary application
NYM-JClass 1 / 2 (Rigid)IncludedFixed power wiring in conduit or under plaster.
NYM-OClass 1 / 2 (Rigid)OmittedControl and signaling circuits without earth requirement.
NYM-KClass 5 (Flexible)J or O variantsIndustrial machinery wiring and panel-to-machine leads.
VDE Market Staples

Standard Export Configurations

These specifications represent the primary volume drivers for residential and light-industrial German-standard projects.

3G1.5 NYM-J (Rigid)

Standard: VDE 0281-1.
· Cores: 3 (Brown, Blue, Green/Yellow)
· Conductor: Class 1 solid
· Common use: Lighting and socket feeds in plaster or conduit.

3G2.5 NYM-K (Flexible)

Standard: VDE 0281-3 equivalent.
· Conductor: Class 5 fine-stranded
· Flexing bending radius: 6× OD
· Common use: Machinery power leads and panel internal wiring.

Engineering Anatomy

The NYM Family: Rigid (NYM) vs. Flexible (NYM-K)

Lead-free PVC compound
RoHS compliant — no restricted substances
REACH — no SVHC substances
IEC 60332-1-2:2004 flame retardant
BIS IS 694:2010 certified production
Technical Specification

Construction and electrical characteristics.

ParameterValue
StandardDIN VDE 0281-1 · IEC 60227 equivalent construction
Rated voltage (U₀/U)300/500V
ConductorPlain annealed copper · Class 1, 2, or 5 (Flexible) · IEC 60228 / IS 8130.
Conductor sizes1.5mm², 2.5mm², 4mm², 6mm², 10mm², 16mm², 25mm², 35mm²
InsulationPVC Type TI1 · colour coded per DIN VDE 0293/HD 308
SheathPVC — grey (standard) · round construction
Core count1, 2, 3, 4, 5 core (standard) · up to 12 core available
Max conductor temperature70°C continuous · 160°C short circuit (5s)
Test voltage2.0kV AC (1 min)
Flame retardantIEC 60332-1-2:2004 / IEC/EN 60332-1
Min installation temp+5°C (bending/installation) · −40°C (fixed service)
Min bending radius6 × OD (installation) · 4 × OD (fixed, after installation)
Sheath colourGrey (standard) · can be supplied black or white on order

MTO sequential meter marking and custom VDE-compliant inkjet strings available for site accountability.

Core Colour Identification

Standard core colour coding — per DIN VDE 0293 / HD 308 S2.

Core CountNYM-J (with earth)NYM-O (without earth)
2-coreBrown + BlueBrown + Blue
3-coreBrown + Blue + Green/YellowBrown + Black + Grey
4-coreBrown + Black + Grey + Green/YellowBrown + Black + Grey + Blue
5-coreBrown + Black + Grey + Blue + Green/YellowBrown + Black + Grey + Blue + Black

IS 694:2010 domestic multicore colour code (Red/Yellow/Blue/Black/Green) differs from DIN VDE 0293. Export NYM is manufactured with DIN VDE colour coding as standard.

IS 694:2010 vs NYM — Voltage advantage
Same TI1 PVC insulation. Same conductor class. IS 694:2010 certifies the same construction at 650/1100V — NYM is rated 300/500V.
IS 694:2010 multicore and NYM share identical insulation wall thicknesses at every cross-section, the same IEC 60228 copper conductor class, and the same TI1 PVC insulation compound. IS 694:2010 tests to 2.5kV; NYM tests to 2.0kV. Same physical cable — IS 694:2010 applies a more conservative voltage classification and a higher proof test.
DIN VDE 0281-1 (NYM) IS 694:2010 base production IEC 60228 conductors PVC TI1 — identical insulation 2.5kV test (IS) vs 2.0kV (NYM) 650/1100V vs 300/500V
Insulation Thickness — IS 694:2010 vs NYM

Same wall thickness. Higher voltage rating.

Size (mm²)NYM insulation (300/500V)IS 694:2010 insulation (650/1100V)NYM test voltageIS 694:2010 test voltage
1.50.7 mm0.7 mm2.0 kV2.5 kV
2.50.8 mm0.8 mm2.0 kV2.5 kV
4.00.8 mm0.8 mm2.0 kV2.5 kV
6.00.8 mm0.8 mm2.0 kV2.5 kV
10.01.0 mm1.0 mm2.0 kV2.5 kV
16.01.0 mm1.0 mm2.0 kV2.5 kV
25.01.2 mm1.2 mm2.0 kV2.5 kV

Same physical construction, certified to a higher dielectric standard. National Cables applies a 3.0kV AC routine test to all MTO NYM orders, exceeding the VDE 2.0kV baseline.

Dimensional Reference

3-core OD: rigid NYM-J vs. flexible NYM-K.

Class 5 flexible conductors yield a slightly larger overall diameter (OD) than rigid Class 1/2 NYM-J for the same copper cross-section — a key detail for engineering contractors at the design stage. Reference per DIN VDE 0281-1 / project datasheets; confirm on MTO release.

Size (mm²) Insul. (mm) NYM-J (Rigid) 3-core OD NYM-K (Flex) 3-core OD Max R Rigid (Ω/km) Max R Flex (Ω/km)
1.50.79.19.512.113.3
2.50.810.410.97.417.98
4.00.812.012.54.614.95

6–35mm², 4/5-core, and 7/10/12-core rigid matrices — contact us for full dimensional and weight data.


Current Carrying Capacity

3-core NYM-J — rated current, 70°C PVC, per IEC 60364-5-52.

Values per IEC 60364-5-52 Table B.52.4 for 3 loaded copper conductors, PVC insulation, 70°C conductor, 30°C ambient.

Size (mm²) Method B (A)
Conduit on wall / trunking
Method C (A)
Clipped direct to surface
Method E (A)
Free air / perforated tray
Max R Ω/km
1.513.517.51812.1
2.51824247.41
4.02432324.61
6.03141403.08
10.04257541.83
16.05676731.15
25.07396950.727
35.0891191170.524

Method B: multicore enclosed in conduit on wall or in trunking. Method C: multicore clipped direct to surface. Method E: multicore in free air or on perforated tray.

De-rating Factors

Ambient temperature correction — 70°C PVC.

Values above at 30°C ambient. Multiply the tabulated rating by the factor for your site ambient temperature.

Ambient Temp
Factor
25°C
1.03
30°C
1.00
35°C
0.94
40°C
0.87
45°C
0.79
50°C
0.71

Per IEC 60364-5-52 Table B.52.14 (70°C thermoplastic PVC). Example: 4mm² NYM-J clipped direct at 45°C ambient: 32 × 0.79 = 25A.


Markets

Where NYM is specified.

Approved NYM-J feeds for LCL/FCL project supply to UAE, Jordan, and East Africa.

Central Europe
Germany, Austria, Switzerland
Primary specification — DIN VDE dominant
Eastern Europe
Poland, Czech Republic, Hungary
DIN VDE / VDE-influenced specifications
Middle East & Gulf
UAE, Turkey, Jordan, Lebanon
German standard influence. Approved NYM-J feeds for LCL/FCL project supply.
East Africa
Ethiopia, Sudan, Eritrea, Kenya
German infrastructure influence. Approved NYM-J feeds for LCL/FCL project supply.
North Africa
Tunisia, Algeria, Libya
Mixed IEC / VDE specifications
Southeast Europe
Romania, Bulgaria, Serbia
VDE / IEC mixed market

Safety Upgrade

Looking for Halogen-Free?

For metro, hospital, and airport projects requiring zero-halogen performance, we supply the (N)HM-J sheathed LSZH equivalent. View the LSZH Building Wire Family →

Frequently Asked Questions

NYM VDE 0281 building cable — technical questions answered.

Common questions from electrical contractors, engineers, and importing partners specifying NYM family cables to VDE 0281 for German-market and European building projects.

What is the difference between NYM-J, NYM-O, and NYM-K?

NYM-J — Multi-core sheathed cable with protective earth core (green/yellow conductor). Specified for residential and commercial power distribution where grounding is required by building code. Class 1 (solid) or Class 2 (stranded) conductor options; common configurations include 3G1.5, 3G2.5.

NYM-O — Same construction as NYM-J but without earth core. Used for signaling, control circuits, and lighting feeds in systems that don't require a separate protective conductor. Also available in Class 1 and Class 2.

NYM-K — Class 5 fine-stranded flexible variant of NYM-J or NYM-O. Used for machinery power leads, panel-internal wiring, and applications requiring repeated bending. Meets VDE 0281-3 flexibility requirements with 6× OD bending radius during installation.

What is VDE 0281 and why is it important for German and European projects?

VDE 0281 is the German Institute for Electrotechnology (Verband der Elektrotechnik Elektronik Informationstechnik) standard for sheathed round installation cables. It specifies construction, materials (PVC insulation and sheath), voltage rating (300/500V), flame performance (IEC 60332-1-2), and conductor sizing per IEC 60228.

VDE 0281 cables dominate German, Austrian, Eastern European, and Middle Eastern building markets. Many national building codes reference or adopt VDE 0281 specifications. Non-VDE compliant cables are typically rejected at site inspection in these markets.

National Cables manufactures NYM family to full VDE 0281 specification with BIS certification and third-party testing for export conformance.

What is the maximum operating temperature and current rating for NYM cable?

Continuous rating: 70°C maximum conductor temperature at 30°C ambient. This is standard for PVC Type TI1 insulation per VDE 0281.

Short-circuit rating: 160°C for 5 seconds maximum during fault conditions.

Current capacity: Depends on conductor cross-section and ambient temperature. A 3G2.5 NYM-J in free air at 30°C carries approximately 20–25A; derating applies proportionally above 30°C ambient. Refer to published current-carrying tables for specific sizing or contact us for technical guidance.

Installation temperature minimum is +5°C (bending/pulling) and −40°C (fixed service).

Can NYM cable be directly buried or installed in damp environments?

NYM per VDE 0281 is not recommended for direct burial or prolonged submersion. The PVC outer sheath provides moisture resistance but is not rated as a direct-burial sheath; cable jacket degradation occurs over time in wet soil.

For outdoor/damp installations:

  • Underground runs: Use NYCY (with copper earthing tape) inside conduit or protective duct.
  • Exposed damp locations: Install inside rigid conduit or wall-mounted trunking to protect from UV and moisture.
  • Wet areas (kitchens, bathrooms): Embed in plaster or install behind water-resistant wall paneling.

Contact our technical team for damp-environment cable selection if standard NYM doesn't fit your application.