IEC 60502-1 · VDE 0276-603 · 0.6/1kV · Power Cable · Export Range

NYY-J / NYY-O
0.6/1kV unarmoured power cable for fixed installations.

NYY is the European standard for unarmoured PVC power cable at 0.6/1kV — the direct equivalent of multicore power cable for indoor fixed installation, cable tray, duct, and underground in conduit. Used across Europe, GCC, North Africa, and East Africa for power distribution and control circuits. The heavy-duty sheathed counterpart to the lighter NYM building cable.

0.6/1kV
Rated voltage — IEC 60502-1
70°C
Max conductor temperature
1.5–240mm²
Conductor size range
1–5 core
Standard core counts
IS 694:2010 — BIS certified production (CM/L-8800140116). All NYY export builds utilize our BIS-certified electrolytic copper and TI1 PVC insulation platform. Manufactured to 1100V working voltage, providing a verified dielectric margin over the standard 1000V NYY specification.
NYY vs NYM — Critical Distinction

NYY and NYM — different standard, different voltage class, different application.

NYM and NYY appear in the same procurement categories and are often interchanged by specifiers. The technical difference:

ParameterNYMNYY
StandardDIN VDE 0281IEC 60502-1 / VDE 0276-603
Voltage rating300/500V0.6/1kV (600/1000V)
Insulation thicknessThinner — 300/500V classThicker — 0.6/1kV class (0.8–1.0mm)
Sheath thicknessThinner — indoor buildingThicker — 1.8mm nominal (outdoor capable)
Direct burialNot suitablePermitted per VDE 0276-603; conduit recommended for high-mechanical stress soil.
Test voltage2.0kV3.5kV (IEC 60502-1)
ApplicationBuilding internal wiringPower distribution, outdoor, underground in conduit
Technical Specification

Construction and electrical characteristics — NYY to IEC 60502-1.

ParameterValue
StandardIEC 60502-1 Edition 3:2021 · VDE 0276-603 · HD 603 S1
Rated voltage (U₀/U)0.6/1kV (600V conductor-to-earth / 1000V conductor-to-conductor)
ConductorPlain annealed copper · Class 1 (≤10mm²) or Class 2 (≥16mm²) · IEC 60228
Insulation compoundPVC/A (DIV 4 per HD 603) — 0.8mm (1.5–6mm²) · 1.0mm (10–16mm²)
FillerPVC or non-hygroscopic extruded filler — round cross-section maintained
Inner beddingExtruded PVC or tape — between cores and outer sheath
Outer sheathPVC compound DMV5 · 1.8mm nominal (3–5 core standard sizes)
Sheath colourBlack (standard)
Max conductor temperature70°C continuous · 160°C short circuit (5s)
Test voltage3.5kV AC (1 min) per IEC 60502-1
Flame retardantIEC 60332-1-2:2004 / EN 60332-1
Min bending radius12 × OD (multicore) · 15 × OD (single core)
Min installation temp−5°C (flexing) · −40°C (static)
MTO builds include standard sequential meter marking and NC internal batch traceability inkjet strings.
Construction Diagram

Cross-section — NYY 3-core.

National Cables NYY Power Cable Precision Drawing | 3.5kV Test Platform HD PVC SHEATH (TYPE DMV5) 0.6/1kV RIGID PROPRIETARY NYY SPEC: NC
Copper conductors — Class 1 solid (RE, ≤10mm²) / Class 2 stranded (RM, ≥16mm²)
PVC filler — round cross-section maintained
Black PVC outer sheath — DMV5 compound
Cores: Brown · Black · Grey (3-core) · + Green/Yellow earth (NYY-J)
Dimensional Data — Multicore Configurations

Full configuration table — cores, sizes, OD, and weight.

All values from Eland Cables NYY-J datasheet (primary reference, 6-page PDF). RE = Class 1 solid copper · RM = Class 2 stranded copper.

CoresSize (mm²)Conductor Insulation (mm)Sheath (mm) OD (mm)Weight (kg/km)
12.5RE (Class 1 solid)0.81.46.1562
14.0RE (Class 1 solid)1.01.47.585
16.0RE (Class 1 solid)1.01.47.5108
110.0RM (Class 2 stranded)1.01.48.6155
116.0RM (Class 2 stranded)1.01.49.6218
125.0RM (Class 2 stranded)1.21.411.1318
135.0RM (Class 2 stranded)1.21.412.1414
150.0RM (Class 2 stranded)1.41.413.7552
170.0RM (Class 2 stranded)1.41.415.5750
195.0RM (Class 2 stranded)1.61.517.61020
21.5RE (Class 1 solid)0.81.810.0147
22.5RE (Class 1 solid)0.81.810.7179
24.0RM (Class 2 stranded)1.01.813.0268
26.0RM (Class 2 stranded)1.01.814.2337
210.0RM (Class 2 stranded)1.01.816.2472
216.0RM (Class 2 stranded)1.01.818.2644
31.5RE (Class 1 solid)0.81.810.4166
32.5RE (Class 1 solid)0.81.811.3212
34.0RE (Class 1 solid)1.01.813.1299
36.0RE (Class 1 solid)1.01.815.0402
310.0RM (Class 2 stranded)1.01.817.1570
316.0RM (Class 2 stranded)1.01.819.2789
325.0RM (Class 2 stranded)1.21.822.11141
335.0RM (Class 2 stranded)1.21.824.11462
350.0RM (Class 2 stranded)1.41.827.61964
41.5RE (Class 1 solid)0.81.811.6198
42.5RE (Class 1 solid)0.81.812.1252
44.0RM (Class 2 stranded)1.01.815.1391
46.0RM (Class 2 stranded)1.01.816.5465
410.0RM (Class 2 stranded)1.01.818.6702

Configurations above 5-core, 7-core, 12-core, and up to 27-core available on enquiry.

Current Carrying Capacity

3-core NYY — rated current, 70°C PVC, per IEC 60364-5-52.

Values per IEC 60364-5-52 Table B.52.4 for 3 loaded copper conductors, PVC insulation, 70°C conductor, 30°C ambient. Apply de-rating for higher ambient temperatures — see below.

Size (mm²) Method B (A)
Conduit on wall/trunking
Method C (A)
Clipped direct
Method E (A)
Free air / cable tray
Max R Ω/km
1.513.517.51812.1
2.51824247.41
4.02432324.61
6.03141403.08
10.04257541.83
16.05676731.15
25.07396950.727
35.0891191170.524
50.01081441410.387
70.01361841790.268
95.01642232160.193
120.01882592490.153
150.02162992850.124
185.02453413240.0991
240.02864033800.0754

Method B: multicore cable enclosed in conduit on a wall or in trunking. Method C: multicore cable clipped direct to surface. Method E: multicore cable in free air or on perforated tray.

De-rating Factors

Ambient temperature correction — PVC 70°C.

Multiply the tabulated rating by the factor for your site ambient temperature. Critical for outdoor and buried installations in Africa and the Gulf.

Ambient Temp
Factor
25°C
1.03
30°C
1.0
35°C
0.94
40°C
0.87
45°C
0.79
50°C
0.71
55°C
0.61
60°C
0.5
IS 694:2010 Production Platform — What It Covers and Where
IS 694:2010 insulation wall directly matches IEC 60502-1 NYY requirements at most sizes. Only 4mm² and 6mm² need an adjusted wall setting.
National Cables manufactures to IS 694:2010 (BIS certified). For NYY export, the same BIS-certified copper conductors and PVC compound are used — the production alignment is strong across most of the size range. At 1.5mm² and 2.5mm², IS 694:2010 specifies 0.8mm insulation — exactly matching the IEC 60502-1 PVC/A requirement. At 10mm² to 35mm², IS 694:2010 specifies 1.0mm and 1.2mm respectively — again exactly matching IEC 60502-1. At 4mm² and 6mm² only, IS 694:2010 specifies 0.8mm while IEC 60502-1 requires 1.0mm. For these two sizes, the extrusion is run at the IEC 60502-1 insulation wall (1.0mm) using the same copper and compound — the conductor quality assurance remains IS 694:2010 certified throughout. All NYY export product is tested to the 3.5kV IEC 60502-1 test voltage.
1.5 & 2.5mm² — IS 694:2010 wall matches IEC 60502-1 4 & 6mm² — IEC wall setting (1.0mm), IS copper 10mm²+ — IS 694:2010 wall matches IEC 60502-1 IS 694:2010 certified copper throughout 3.5kV IEC 60502-1 test voltage — all sizes
Size-by-size IS 694:2010 coverage for NYY:
SizeIS 694:2010 wallIEC 60502-1 wallStatus
1.5 & 2.5mm²0.8mm0.8mm✓ IS 694:2010 direct
4 & 6mm²0.8mm1.0mm→ IEC wall setting, IS 694:2010 copper
10 & 16mm²1.0mm1.0mm✓ IS 694:2010 direct
25mm²+1.2mm1.2mm✓ IS 694:2010 direct
EPC & Infrastructure Services

Custom Project Engineering for GCC & Africa

National Cables provides specialized technical enhancements for large-scale power distribution.

UV-Stabilized Sheathing

For high-exposure desert or tropical environments, our DMV5 PVC sheath is enhanced with carbon-black additives to meet international UV resistance standards, preventing premature embrittlement in outdoor tray installations.

Custom Drum Management

To minimize site joints and cable wastage, we supply NYY on custom drum lengths tailored to your site-specific pull-schedules. Export drums are ISPM-15 fumigated and treated for termite protection as standard.

Markets

Where NYY is specified.

GCC / Gulf
UAE, Saudi Arabia, Qatar, Kuwait
IEC 60502-1 power cable specification
North Africa
Egypt, Morocco, Libya, Tunisia
IEC 60502 / HD 603 standard market
East Africa
Kenya, Tanzania, Uganda
IEC alongside BS — NYY used for power
West Africa
Nigeria, Ghana, Senegal
IEC 60502 / project specification
Europe
All IEC/VDE markets
HD 603 / IEC 60502-1
Central Asia
Kazakhstan, Uzbekistan
IEC / VDE specifications
Frequently Asked Questions

NYY multi-core power cable — technical questions answered.

Common questions from electrical engineers, utility companies, and importing partners specifying NYY cables for power distribution, grid interconnection, and industrial installations across Africa, Middle East, and Asia.

What is NYY cable and where is it used?

NYY cable is a multi-core power distribution cable with PVC insulation and PVC outer sheath, designed for fixed underground and above-ground applications. The designation follows German/European coding: N = Standard installation cable (Normleitung) · Y = PVC insulation · Y = PVC sheath.

Typical applications:

  • Underground power distribution: Primary and secondary feeder cables in utility distribution networks, buried without additional protection.
  • Industrial power circuits: Fixed factory wiring, large motor feeder cables, substation interconnects.
  • Outdoor above-ground runs: Pole-mounted distribution feeders, cross-country transmission links.
  • High-current fixed installations: Where flexibility is not required and voltage drop must be minimized.

NYY is dominant in African, Middle Eastern, and Asian markets where IEC 60502-1 or IEC 60227-2 adoption is widespread.

What is the difference between NYY and NYM cable?

NYY: Multi-core power cable with Class 1 (solid) or Class 2 (stranded) conductors. Larger cross-sections (1.5–240mm²+). 450/750V to 6/10kV depending on variant. Designed for fixed, high-current power distribution. Not flexible — solid construction optimizes current density.

NYM: Multi-core sheathed building cable with Class 1/2 conductors. Smaller cross-sections (1.5–35mm²). 300/500V rated. Designed for general building power wiring and low-voltage circuits. Slightly more flexible than NYY but still not for repeated bending.

Key distinction: NYY = power distribution infrastructure (utilities, industrial). NYM = building installation wiring. NYY carries larger currents at higher voltages; NYM is general-duty building circuit.

Can NYY cable be buried directly in soil, or does it require conduit?

NYY per IEC 60502-1 and IEC 60227-2 is approved for direct burial in soil without additional conduit or protective duct. The PVC outer sheath is rated for soil contact and provides adequate moisture and mechanical protection for permanent underground installations.

Best practice for direct burial:

  • Bury at minimum 0.7–1.0 metre depth to prevent accidental excavation damage.
  • Use warning tape at 0.3 metres above cable to alert diggers.
  • Keep cable away from sharp rocks and aggressive soil (highly acidic, caustic soda, lime-rich environments).
  • In high-disturbance areas, install in conduit for added protection despite IEC approval for direct burial.

Above-ground installations typically use cable trays or clips to avoid UV damage; exposure to direct sunlight degrades the PVC sheath over time.

What are the current ratings and derating factors for NYY cable?

Current-carrying capacity depends on conductor cross-section, number of cores, and installation method (buried, above-ground, in conduit, etc.).

Example ratings (3-core cable, buried 0.7m, 30°C soil temperature):

  • 3×4mm²: approximately 50A
  • 3×6mm²: approximately 68A
  • 3×10mm²: approximately 96A
  • 3×16mm²: approximately 135A

Derating: Above 30°C (buried soil or ambient), apply temperature factors (0.87 at 35°C, 0.74 at 45°C, 0.62 at 55°C). Multiple-cable bunching also reduces capacity. Contact us for precise derating tables for your specific installation scenario and burial depth.

Enquire for NYY export supply.